Cycle and response times
7.2 Cycle time
7.2.4 Communication Load
Configured communication load (PG/OP communication)
The CPU operating system continuously provides a specified percentage of total CPU
processing performance (time-sharing technology) for communication tasks. Processing
performance not required for communication is made available to other processes.
In the hardware configuration, you can set the load due to communications between 5% and
50%. Default value is 20%.
You can use the following formula for calculating the cycle time extension factor:
100 / (100 - configured communication load in %)
8VHUSURJUDPLQWHUUXSW
3HUFHQWDJHFDQEHSDUDPHWHUL]HG
EHWZDQG
7LPHVOLFHPV
&RPPXQLFDWLRQ
8VHU3URJUDP
2SHUDWLQJV\VWHP
Figure 7-3 Breakdown of a time slice
Example: 20% communication load
You have configured a communication load of 20% in the hardware configuration.
The calculated cycle time is 10 ms.
Using the above formula, the cycle time is extended by the factor 1.25.
Example: 50 % communication load
You have configured a communication load of 50 % in the hardware configuration.
The calculated cycle time is 10 ms.
Using the above formula, the cycle time is extended by the factor 2.
S7-300 CPU Data: CPU 315T-2 DP
Manual, 12/2005, A5E00427933-02
7-7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP and is the answer not in the manual?

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP Specifications

General IconGeneral
Programming LanguageSTEP 7
Power Supply24 V DC
Number of DP masters1
Processable Technology objectsYes
Number of counters256
Number of timers256
S7 communicationYes
Number of connections for S7 communication, max.16
PG/OP communicationYes
Global data communicationYes
Integrated DP interfaceYes
Integrated PROFINET interfaceNo
SIMATIC Computing PlatformNo
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
CommunicationPROFIBUS DP
Cycle Time0.1 ms
Engineering withSTEP 7
Backup availableYes
Transmission rate, max.12 Mbit/s

Related product manuals