Cycle and response times
7.2 Cycle time
Physical cycle time depending on communication load
The figure below describes the non-linear dependency of the physical cycle time on
communication load. As an example, we have chosen a cycle time of 10 ms.


  


 PV
 PV
 PV
 PV
P
s
 PV

<RXFDQVHWWKHFRPPXQLFDWLRQORDGLQWKLV
UDQJH
&RPPXQLFDWLRQORDG
&\FOHWLPH
Figure 7-4 Dependency of the Cycle Time on the Communication Load
Influence on the physical cycle time
Due to the increase in the cycle time as a result of the communications component, even
more asynchronous events occur, from a statistical point of view, within an OB 1 cycle than,
say, interrupts. This further extends the OB1 cycle. This extension depends on the number
of events that occur per OB1 cycle and the time required to process these events.
Note
Change the value of the "communication load" parameter to check the effects on the cycle
time at system runtime. You must consider the communication load when you set the
maximum cycle time, otherwise timing errors may occur.
Tips
If possible, apply the default value.
Increase this value only if the CPU is used primarily for communications and if the user
program is not time critical.
In all other situations you should only reduce this value.
S7-300 CPU Data: CPU 315T-2 DP
7-8 Manual, 12/2005, A5E00427933-02

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP and is the answer not in the manual?

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP Specifications

General IconGeneral
Programming LanguageSTEP 7
Power Supply24 V DC
Number of DP masters1
Processable Technology objectsYes
Number of counters256
Number of timers256
S7 communicationYes
Number of connections for S7 communication, max.16
PG/OP communicationYes
Global data communicationYes
Integrated DP interfaceYes
Integrated PROFINET interfaceNo
SIMATIC Computing PlatformNo
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
CommunicationPROFIBUS DP
Cycle Time0.1 ms
Engineering withSTEP 7
Backup availableYes
Transmission rate, max.12 Mbit/s

Related product manuals