Memory concept
6.1 Memory areas and retentive address areas
Properties of an MMC
The MMC ensures maintenance-free and retentive operation of these CPUs.
Caution
Data on a SIMATIC Micro Memory Card can be corrupted if you remove the card while it is
being accessed by a write operation. In this case, you may have to delete the MMC on your
PG, or format the card in the CPU.
Never remove an MMC in RUN mode. Always remove it when power is off, or when the CPU
is in STOP state, and when the PG is not a writing to the card. When the CPU is in STOP
mode and you cannot not determine whether or not a PG is writing to the card (e.g.
load/delete block), disconnect the communication lines.
MMC copy protection
Your MMC has an internal serial number that provides copy protection at user level. You can
read this serial number from the SSL partial list 011C
H
index 8 using SFC 51 "RDSYSST."
You can then program a STOP command, for example, in a copy-protected block if the
expected and actual serial numbers of your MCC do not tally.
Reference
Further information
can be found in the
SSL partial list in the instruction list,
or
in the
System and Standard Functions
manual.
Useful life of an MMC
The useful life of an MMC is determined in particular by the following factors:
The number of delete or programming operations,
external influences such as the ambient temperature.
At ambient temperatures up to 60 °C, a maximum of 100,000 delete/write operations can be
performed on an MMC.
Caution
in order to prevent data losses, do not exceed this maximum of delete/write operations.
S7-300 CPU Data: CPU 315T-2 DP
6-8 Manual, 12/2005, A5E00427933-02

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP and is the answer not in the manual?

Siemens SIMATIC S7-300 CPU Data: CPU 315-T-2 DP Specifications

General IconGeneral
Programming LanguageSTEP 7
Power Supply24 V DC
Number of DP masters1
Processable Technology objectsYes
Number of counters256
Number of timers256
S7 communicationYes
Number of connections for S7 communication, max.16
PG/OP communicationYes
Global data communicationYes
Integrated DP interfaceYes
Integrated PROFINET interfaceNo
SIMATIC Computing PlatformNo
Operating Temperature0 to 60 °C
Integrated InterfacesMPI, DP
CommunicationPROFIBUS DP
Cycle Time0.1 ms
Engineering withSTEP 7
Backup availableYes
Transmission rate, max.12 Mbit/s