Programming Example for Standard Function Blocks   
9.5 Installation, Error Messages 
  Point-to-point connection CP 440 Installation and Parameter Assignment 
132  Manual, 09/2007, A5E00057742-03 
9.5 Installation, Error Messages 
Scope of Supply and Installation 
The project example of the CP 440 and the CP 440: Point -to-Point Communication, 
Parameter Assignment interface is supplied together with the function blocks and this 
manual on a CD. 
The program examples are installed together with the parameter assignment interface and 
desribed in Section 3.3. After installation, the examples are stored in the following project: 
CP440_PtP_Com 
Open the project in SIMATIC Manager of STEP 7 by selecting the File > Open > Project
menu command.  
The project example is available both compiled and as a source file. A list of all the symbols 
used in the example is also included. 
If you do not have access to a second CP 440 as communication partner, open the 
HW Config and remove the CP 440 with the Edit > Delete < menu command. The call of the 
FC 22 (FC for Receive) must also be commented out of the examples "CP440 
SEND RECV", "CP440 1CYC" and "CP440 ASCII BCC" in OB 1. 
Download to the CPU 
The hardware for the example is completely set up and the programming device is 
connected. 
After the overall reset of the CPU (operating mode STOP), transfer the complete example to 
the user memory. Then use the operating mode switch to change from STOP to RUN. 
Malfunction 
If an error occurs at startup, the cyclically processed block calls are terminated with an error. 
If there is an error message, the parameter output ERROR of the modules is set. A more 
precise error description is then stored in the STATUS parameter of the blocks. If STATUS 
contains one of the error messages 16#1E0E or 16#1E0F, the exact error description is 
stored in the SFCERR variable in the instance DB. 
See also 
Assigning parameters to the CP 440 (Page 65) 