Communication via Function Blocks 
  6.3 Using the Function Blocks 
Point-to-point connection CP 440 Installation and Parameter Assignment 
Manual, 09/2007, A5E00057742-03 
89 
6.3 Using the Function Blocks 
Introduction 
The following sections describe what you must take into account when supplying the function 
blocks with parameters. 
STATUS Indication at the FB 
Please note the following with reference to the STATUS display on the function blocks: 
 
 
Note 
The parameters DONE, NDR, ERROR and STATUS are valid for only one module run. To 
display the STATUS, you should therefore copy it to a free data area. 
DONE = '1' means that the request was completed without error. 
This means: 
●  With ASCII driver: The job was sent to the communication partner. This does not 
necessarily mean that the data was received by the communication partner. 
●  With 3964( R ) procedure: The job was sent to the communication partner and 
acknowledged affirmatively by the communication partner. This does not necessarily 
mean that the data was forwarded to the partner CPU. 
Jobs which can be processed simultaneously 
Only one SEND_440 FB, one RECV_440 FB and one RES_RECV FB can be programmed 
in the user program for each CP 440 used. 
In addition, you can only use the following data blocks because the states required for the 
internal execution of the FB are stored in the instance data block: 
●  1 instance data block for the SEND_440 FB 
●  1 instance data block for the RECV_440 FB 
●  1 instance data block for the RES_RECV FB 
Data Consistency 
Please note the following to ensure consistent data transmission: 
●  Sender: Only access the send DB when all data have been completely transferred 
(DONE = 1). 
●  Receiver: Only access the receive DB when all data are received (NDR = 1). Then you 
must inhibit the receive DB (EN_R = 0) until you have processed the data. 