Configuring and Parameter Assignment the CP 440   
5.4 Configuration data 
  Point-to-point connection CP 440 Installation and Parameter Assignment 
68  Manual, 09/2007, A5E00057742-03 
5.4 Configuration data 
5.4.1 Introduction 
Introduction 
You can set the response of the CP 440 to CPU STOP by means of the basic parameters. 
By selecting different protocols, you can adjust your CP 440 communication processor to suit 
the properties of the communication partner.  
The sections that follow describe the basic parameters of the CP 440 and the configuration 
data for the ASCII driver and for the 3964(R) procedure. 
5.4.2 Basic Parameters of the CP 440 
 
Enter the basic parameters in the STEP 7 HW dialog box "Properties - CP 440 ". Open the 
dialog box by double-clicking the CP 440 in the configuration table of STEP 7. 
The basic parameters are described in the table below. 
Table 5-2  Basic Parameters of the CP 440 
Parameters  Description  Value Range  Default Value 
Reaction to CPU Stop  This parameter controls the storage of 
the received frames in the receive 
buffer. 
You can find more detailed information 
in the following tables. 
• Continue 
• STOP 
 
The transmission process is 
terminated in both cases. 
Continue 
 
Affect of the “Reaction to CPU Stop” Parameter on the Storage of the Received Message Frames 
The response depends on whether or not flow control is used. 
Table 5-3  Control of Message Frame Storage Without Flow Control 
Without Flow Control  Saved Frames  Frame Just Arriving  New Frames 
Reaction to CPU Stop: 
Continue 
Retained  Saved; discarded if the buffer 
is full 
Saved until the buffer is full, 
then discarded 
Reaction to CPU Stop: 
STOP 
Retained  Discarded  Discarded 
 