Configuring and Parameter Assignment the CP 440   
5.6 Firmware updates 
  Point-to-point connection CP 440 Installation and Parameter Assignment 
84  Manual, 09/2007, A5E00057742-03 
5.6.2 Viewing the Firmware Version 
Viewing the Hardware and Firmware Version 
You can view the current hardware and firmware version of the communication processor in 
STEP 7 in the "Module Status" dialog. You can open this dialog by: 
In SIMATIC Manager: File > Open > Project > HW Config > Station > Online > double-click 
on the module of the communication processor. 
LEDs 
LEDs during the download of a firmware update: 
Table 5-15  LEDs for firmware update 
Status  INTF/EXTF  FAULT  TXD  RXD  Remark  To correct or avoid 
errors 
Firmware update in 
progress 
on  on  on  on  -  - 
Firmware update 
completed 
on  off  off  off  -  - 
CP 440 without 
module firmware 
flashes (2 Hz)  on  off  off  Module firmware 
deleted, firmware 
update was canceled, 
firmware update still 
possible 
Reloading the firmware 
Hardware fault during 
firmware update 
flashes (2 Hz)  off  flashes 
(2 Hz) 
flashes 
(2 Hz) 
Read/write operation 
failed 
Switch power supply to 
module off and then on 
again and reload the 
firmware. 
Check whether the 
module is defective. 
 