Communication via Function Blocks   
6.3 Using the Function Blocks 
  Point-to-point connection CP 440 Installation and Parameter Assignment 
96  Manual, 09/2007, A5E00057742-03 
Assignment in the Data Area 
The RECV_440 FB works with an instance DB (I_RECV_440). The DB number is specified in 
the call. The data in the instance DB cannot be accessed.  
 
 
Note 
Exception: If the error (STATUS == W#16#1E0E) occurs, you can consult the SFCERR 
variable for more details of the error. This error variable can only be loaded via a symbolic 
access to the instance DB. 
Parameters of the RECV_440 FB 
The following table lists the parameters of the RECV_440 FB. 
Table 6-5  Parameters of the RECV_440 FB 
Name  Type  Data type  Description  Permitted Values, Comment 
EN_R  INPUT  BOOL  Enables data read   
R  INPUT  BOOL  Aborts request  Current request is aborted. Receiving is 
blocked. 
LADDR   INPUT  INT  Basic address of CP 440  The basic address can be found in the 
configuration table in STEP 7. 
DB_NO  INPUT  INT  Data block number  Receive DB No.: 
CPU-specific, zero is not allowed 
DBB_NO  INPUT  INT  Data byte number  Offset is CPU-specific 
NDR 
1
  OUTPUT  BOOL  Request completed without 
errors, data accepted 
STATUS parameter == 16#00; 
ERROR 
1
  OUTPUT  BOOL  Request completed with 
errors 
STATUS parameter contains error details 
LEN 
1
  OUTPUT  INT  Length of message frame 
received 
1 ≤ LEN ≤ 400 (Page 86),  
specified in number of bytes 
STATUS 
1
  OUTPUT  WORD  Error specification  If ERROR == 1, STATUS parameter contains 
error details 
1 
The parameter is available until the next call of the FB! 
 