Mounting the CP 440   
4.2 Mounting and Dismounting the CP 440 
  Point-to-point connection CP 440 Installation and Parameter Assignment 
62  Manual, 09/2007, A5E00057742-03 
4.2 Mounting and Dismounting the CP 440 
Introduction 
When mounting and removing the CP 441, you must observe certain rules. 
Tool 
You will need a 3.5 mm cylindrical screwdriver to mount or dismount the communication 
processor. 
 
 
Note 
The CP 440 can be hot-plugged and hot-pulled, in other words with voltage applied. This 
means that the CP 440 can be replaced while the programmable logic controller is in 
operation. To avoid the CPU going into STOP, OB 83 (insert/remove interrupt) and OB 122 
(I/O access error) must be programmed.The CP 440 is configured automatically when it is 
plugged in. The CP 440 then resumes operation. 
Installation Guidelines 
The general installation guidelines for S7-400 must be observed (see the 
S7-400/M7-400 
Programmable Controller, Hardware and Installation
 manual). 
To meet the EMC (electromagnetic compatibility) values, the cable shield must be connected 
to a shield bus. 
4.2.1 Installation steps 
To mount the communication processor in a rack, proceed as follows: 
1. Remove the filler panel from the slot you want to use by gripping it where marked and 
pulling it toward you. Insert the CP 441 module and tilt it downward. 
2. Hang the communication processor in the rack and swing it down. 
3. Screw down the module at the top and bottom with a torque of 0.8 to 1.1 Nm. 
该文档是极速PDF编辑器生成,
如果想去掉该提示,请访问并下载:
http://www.jisupdfeditor.com/