Basic Principles of Serial Data Transmission   
2.5 Data Transmission with the 3964(R) Procedure 
  Point-to-point connection CP 440 Installation and Parameter Assignment 
48  Manual, 09/2007, A5E00057742-03 
2.5.4 Receiving Data with 3964(R) 
Process of Data Transmission when Receiving 
The figure below illustrates the transmission sequence when data is received with the 
3964(R) procedure. 
&3
67;
'/(
'/(
(7;
%&&
'/(
Ⴠ
Ⴠ
Ⴠ
Ⴠ
&RPPXQLFDWLRQ
SDUWQHU
VWE\WH
QGE\WH
VWGDWDE\WH
QGGDWDE\WH
QWKE\WH QWKGDWDE\WH
6WDUWFRGH+
3RVDFNQRZOHGJPHQW+
(QGFRGH+
(QGFRGH+
5RQO\
3RVDFNQRZOHGJPHQW+
&RQQHFWLRQ
VHWXS
8VHU
GDWD
&RQQHFWLRQ
FOHDUGRZQ
 
Figure 2-15  Data Traffic when Receiving with the 3964(R) Procedure 
 
 
 
Note 
As soon as it is ready, the 3964(R) procedure sends a single NAK to the communication 
partner to set the latter to idle. 
Establishing a Receive Connection 
In idle mode, when there is no send request to be processed, the procedure waits for the 
communication partner to establish the connection. 
If no empty receive buffer is available during a connection setup with STX, a wait time of 
400 ms is started. If there is still no empty receive buffer after this time has elapsed, the 
CP 440 reports the error (error message at the STATUS output of the FB) and the procedure 
sends a NAK and returns to idle mode. Otherwise, the procedure sends a DLE and receives 
the data. 
If the idle procedure receives any control code except for STX or NAK, it waits for the 
character delay time to expire, then sends the code NAK. The CP 440 reports the error to 
the RECV_440 function block (STATUS output parameter). 