Technical Specifications
A.2 Transmission Rates
Point-to-point connection CP 440 Installation and Parameter Assignment
Manual, 09/2007, A5E00057742-03
141
A.2 Transmission Rates
Transmission Rates
The tables below indicate the transmission times required depending on the transmission
protocol selected.
Two S7-400s each with a CPU 416 (6ES7 416-2XK02-0AB0) and a CP 440 were used to
measure the times. A SEND_440 FB was programmed in the user program of the active
CPU, and a RECV_440 FB was programmed in the user program of the passive CPU. The
time that elapsed between the initiation and completion of the request was measured.
ASCII Driver
Transmission times with the ASCII driver:
Table A-4 Transmission Times with the ASCII Driver in ms
Baud rate (bd) User data
115200 76800 57600 38400 19200 9600 4800 2400 1200 600 300
1 bytes 1,5 2 2 2 3 4 8 15 29 55 110
10 bytes 2 2 3 5 8 14 28 56 111 220 440
20 bytes 4 5 6 8 14 26 52 102 202 404 807
50 bytes 6 9 12 17 32 60 120 240 478 952 1906
100 bytes 12 17 22 32 61 118 236 470 936 1872 3740
200 bytes 22 32 41 59 117 230 460 920 1835 3668 7330
3964(R) Procedure
Transmission times with the 3964(R) procedure:
Table A-5 Transmission Times with the 3964(R) Procedure in ms
Baud rate (bd) User data
115200 76800 57600 38400 19200 9600 4800 2400 1200 600 300
1 bytes 4 4 5 7 9 11 20 35 68 134 264
10 bytes 5 5 7 8 14 22 40 77 150 296 594
20 bytes 6 7 8 10 20 33 64 122 242 484 960
50 bytes 9 11 14 20 36 68 132 260 518 1032 2060
100 bytes 14 19 24 34 64 126 248 490 976 1949 3894
200 bytes 24 34 44 64 118 240 476 948 1894 3780 7558