Basic Principles of Serial Data Transmission
2.3 Transmission integrity
Point-to-point connection CP 440 Installation and Parameter Assignment
28 Manual, 09/2007, A5E00057742-03
Transmission Integrity with the ASCII Driver
Data Integrity When Using the ASCII Driver:
When data is transmitted via the ASCII driver, there are no data integrity precautions
other than the use of a parity bit (can also be canceled, depending on how the character
frame is set). This means that, although this type of data transport has a very efficient
throughput rate, security is not guaranteed.
Using the parity bit ensures that the inversion of a bit in a character to be transmitted can
be recognized. If two or more bits of a character are inverted, this error can no longer be
detected.
To increase transmission integrity, a checksum and length specification for a message
frame can be employed. These measures must be implemented by the user.
A further increase in data integrity can be achieved by means of acknowledgment
message frames in response to send or receive message frames. This is the case with
high-level protocols for data communication (see ISO 7-layer reference model).
Transmission integrity with 3964(R)
Enhanced Data Integrity with the 3964(R) Procedure:
The Hamming distance with the 3964(R) is 3. This measures the integrity of data
transmission.
The 3964(R) procedure ensures high transmission integrity on the data line. This high
integrity is achieved by means of a fixed message-frame set-up and clear-down as well
as the use of a block check character (BCC).
Two different procedures for data transmission can be used, either with or without a block
check character:
data transmission without a block check character: 3964
data transmission with a block check character: 3964R
In this manual, the designation 3964(R) is used when descriptions and notes refer to both
data transmission procedures.