Configuring and Parameter Assignment the CP 440
5.4 Configuration data
Point-to-point connection CP 440 Installation and Parameter Assignment
Manual, 09/2007, A5E00057742-03
71
Parameters Description Value Range Default Value
Monitoring time for
missing end ID
The character delay time is used as
the monitoring time for a missing end
code. This applies to the following
settings for the end code
On Receipt of Fixed Number of
Characters
On Receipt of End Character
Baud
300
600
1200
2400
4800
9600
19200
38400
57600
76800
115200
Character
delay time
(ms)
130
65
32
16
8
4
2
1
1
1
1
End-of-text
character 1
(1)
First end code.
with 7 data bits:
0 to 7FH (Hex)
(2)
8 data bits:
0 to FFH (Hex)
(2)
3 (03H = ETX)
End-of-text
character 2
(1)
Second end code, if specified.
You can configure the following for the
end code:
1stend code AND 2nd end code
1st end code OR 2nd end code
with 7 data bits:
0 to 7FH (Hex)
(2)
with 8 data bits:
0 to FFH (hex)
(2)
0
Message frame
length when
received
(1)
When the end criterion is "fixed
message frame length", the number of
bytes making up a message frame is
defined.
1 to 400 (bytes) 200
Transmission pause
between the
messages related to
the monitoring time
A pause equal to the length of the
monitoring time (for a missing end ID)
is inserted between two message
frames when sending so that the
partner can synchronize (detect receipt
of the message frame).
Yes
No
Yes
(1)
Can only be set if the end criterion is an end-of-text character.
(2)
Depending on whether you set 7 or 8 data bits for the character frame.