Image 7-1 External fan with cover sheet
7.6 Switch on
Trial run
If the period between installation and commissioning is expected to be fairly long, make sure
that water-cooled machines undergo a test run without water cooling.
Procedure
Start up the motor without a load, temporarily. Check the direction of rotation at this point.
As the motor is coasting down, check the mechanical operation for noise and vibration at
the bearings and bearing shields.
Where the motor is running without any mechanical problems, switch it back on again.
Continue to the maximum speed allowed (according to the rating plate).
In case of uneven running or abnormal noise, switch off the machine. Determine the cause
as it coasts.
If the mechanical operation improves immediately after the motor is switched off, the cause
is magnetic or electrical.
Commissioning
7.6 Switch on
SIMOTICS DC 1GG5
Operating Instructions 02/2016 65