EasyManua.ls Logo

Siemens SIMOTRAS 6SG7050 - Setting the Brake Control

Siemens SIMOTRAS 6SG7050
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start-up 01.04
7-14 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
0
P303
P304
P306 P306 P305
P305 P306 P306
(K0190)
P305
P305P306 P306
P306 P306
P303
P304
Time
+n
set
Clockwise/ Lift
Ant-clockwise / Lower
Fig. 7.6.11.1 Setting the ramp times of the ramp-function generator
Ramp times in closed-loop control range Ramp times in open-loop control range
P303: Ramp-up time
P304: Ramp-down time
P305: Lower transition rounding
P306: Upper transition rounding
P307: Ramp-up time
P308: Ramp-down time
P309: Lower transition rounding
P310: Upper transition rounding
7.6.12 Setting the brake control
The following actions take place after specifying a travel command:
1. The firing pulse and the controller are enabled
2. The “Release brake” signal is output
3. The ramp-function generator starts to ramp up
P087 (with a negative value) can be used to delay the “Release brake” signal in relation to the
enabling of the firing pulse and the controller until the motor has definitely been excited and
torque has developed.
Parameter P319 can be used to delay the ramping up of the ramp-function generator in relation
to the enabling of the firing pulse and the controller using until the brake has definitely been
released (no start-up with brake still closed).
Delay
Delay until brake is released
P319
t
t
t
"Release brake"
signal
Output of ramp-
function
generator with
delayed enable
P087
Controller enable
and firing pulse
enable
(B0250)
(K0190)
Fig. 7.6.12.1 Time characteristic following input of travel command

Table of Contents

Related product manuals