Function descriptions 01.04
9-16 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
9.5.3 Control signals for ramp-function generator
The ramp-function generator operating mode can be preset by the following control signals:
Ramp-function generator start
(control word 1.bit 5):
1 = Setpoint is injected at ramp-function generator input
0 = Ramp-function generator is stopped at current value (generator output is injected as generator
input).
Enable setpoint
(control word 1.bit 6):
1 = Setpoint enabled at ramp-function generator input
0 = Ramp-function generator setting 1 is activated and 0 applied at the input (generator output is
reduced to 0)
Set ramp-function generator:
1 = The ramp-function generator output is set to the setting value (selected in P639)
Enable ramp-function generator
(control word 1.bit 4):
0 = Ramp generator disabled, generator output is set to 0
1 = Ramp-function generator enabled
Ramp-up integrator operation
(parameter P302):
See below and Section 11, Parameter List, parameter P302
Enable switchover of ramp-up integrator
(select via P646):
See below
Ramp-function generator settings 2 and 3
See below
Ramp-function generator tracking ON
(parameter P317):
See below and Section 11, Parameter List, parameter P317
Set ramp-function generator on shutdown
(parameter P318):
See Section 11, Parameter List, parameter P318
Bypass ramp-function generator:
1 = Ramp-function generator operates with ramp-up/ramp-down time of 0
The function is controlled via the binector selected in P641.
The ramp generator can also be bypassed in INCHING, CRAWLING and INJECTION OF FIXED
SETPOINT modes.
9.5.4 Ramp-function generator settings 1, 2 and 3
Selection via binectors selected in parameters P637 and P638
Status of binector
selected by parameter
P637 P638
Ramp function
generator
setting
Effective
runup time
Effective
rundown time
Effective
lower
transition
rounding
Effective
upper
transition
rounding
0 0 1 P303
P304
P305
P306
1 0 2 P307
P308
P309
P310
0 1 3 P311
P312
P313
P314
1 1 Not permitted, activates fault message F041 (selection not clear)
The ramp-function generator settings preset via the binectors selected in P637 and P638 have priority
over the generator setting specified via the ramp-up integrator.
The selection parameter for the switchover to RFG setting 2 is set to 129 in the factory setting (binector
B0129: 0=positive speed setpoint / hoist, 1=negative speed setpoint / lower). Thus, switching takes
place automatically to RFG setting 1 for hoisting and to RFG setting 2 for lowering.