EasyManua.ls Logo

Siemens SIMOTRAS 6SG7050 - Terminal Description

Siemens SIMOTRAS 6SG7050
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connections 01.04
6-30 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
6.7.3 Terminal description
WARNING
The converter might sustain serious or irreparable damage if connected incorrectly.
The power cables and/or busbars must be secured mechanically outside the converter.
Power section Terminal type:
D400 / 60 -180 Mre converters U1, V1, W1: Through-hole for M8 (3x20 copper bus)
U2, V2, W2: Through-hole for M8 (5x20 copper bus)
D400 / 225 -360 Mre converters U1, V1, W1: Through-hole for M10 (5x30 copper bus)
U2, V2, W2: Through-hole for M10 (5x35 copper bus)
D400 / 525 -680 Mre converters Through-hole for M12 (5x60 copper bus)
D400 / 900 Mre converters U1, V1, W1: Through-hole for M12 (10x60 copper bus)
U2, V2, W2: Through-hole for M12 (10x50 copper bus)
The converters are designed for a permanent power supply connection according to DIN VDE 0160
Section 6.5.2.1.
PE conductor connection: Minimum cross-section 10mm
2
. (see Section 5.1 for connection options).
The connection cross-sections must be determined according to the applicable regulations, e.g.
DIN VDE 100 Part 523, DIN VDE 0276 Part 1000.
Function Terminal
Connection values/Remarks
Supply input
PE conductor
Motor connection
U1 (L1)
V1 (L2)
W1 (L3)
U2 (T1)
V2 (T2)
W2 (T3)
see technical data in Section 3.4