01.04 Connections
SIEMENS AG 6SG7000-0BA76 6-31
SIMOTRAS HD Operating Instructions
Electronics power supply
Terminal type: Type 49 plug-in terminal
Maximum cross-section 1.5mm
2
, finely stranded
Function
Connection
Terminal
XP
Connection values/Remarks
Incoming supply
400V
1
2
NC 3
5U1
5W1
5N1
2AC 380V (-25%) to 460V (+15%); I
n
=1A
(– 35% for 1min)
Internal fusing using F1, F2 on the C98043-A7020 module
external fuse protection 6A, characteristic C
recommended
or
Incoming supply
230V
1
2
3
5U1
5W1
5N1
1AC 190V (-25%) to 230V (+15%); I
n
=2A
(– 35% for 1min)
Internal fusing using F1, F2 on the C98043-A7020 module
external fuse protection 6A, characteristic C
recommended
NOTE
In the case of line voltages which exceed the tolerance range specified in Section 3.4, the electronics
supply voltage and converter fan connection must be adjusted by means of transformers to the
permissible value stated in Section 3.4. It is essential to use an isolating transformer for rated line
voltages in excess of 460V.
The rated supply voltage for the power section is to be set in parameter P078 (index 001).
Fan
(for forced-cooled converters ≥ 225A)
Terminal type
: DFK-PC4 plug-in terminal (screw-type)
Maximum connection cross-section 4mm
2
, finely stranded
The insulation on the supply cables must be taken up to the terminal housing.
Function Terminal
Connection values/Remarks
Incoming supply 4U1
4V1
4W1
3AC 400V to 460V
For further details, see technical data in Section 3.4
PE conductor
Fan can be switched via external contactor relay
3TH2031-0FB4 (Siemens), triggered by CUD1 module,
terminals X171 / 46, 47
WARNING
The converter might overheat if the incorrect phase sequence is connected (incorrect direction
of rotation of fan).
Check: Check that the fan is rotating in the direction of the arrow!
Caution: Rotating parts can cause physical injuries!