Connections 01.04
6-32 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Open-loop and closed-loop control section
Terminal type: X171 to X175 Plug-in terminal (screw-type)
Maximum connection cross-section 1.5mm
2
XT, X1, X2_1 to X2_4 MSTB2.5 plug-in terminal
Maximum connection cross-section 2.5mm
2
Analog inputs - setpoint inputs, reference voltage (see also Section 8, sheet G113)
Function Terminal
X174
Connection values/Remarks
Reference M
P10
N10
1
2
3
±1% at 25°C (stability 0.1% per 10°K);
10mA short-circuit-proof
Select input main setpoint +
main setpoint –
4
5
Select input analog 1 +
analog 1 –
6
7
Input type (signal type) parameterizable:
- Differential input ±10V; 150k
- Current input 0 - 20mA; 300
or
4 - 20mA; 300
Resolution can be parameterized up to approx. 555
µV
(±14bit)
Common mode suppression: ±15V
Analog inputs - actual speed inputs, tacho inputs
(see also Section 8, sheet G113)
Function Terminal
XT
Connection values/Remarks
Tacho connection 8V to 270V 103
Ground analog M 104
±270V; >143k