Maintenance 01.04
13-2 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
13.1 Procedure for updating software
(upgrading to a new software version)
1
Read out and write down all parameter
contents.
(also note software version in r060.001 and
r065.001!)
Note:
The parameter set can be transferred to a PC or
programming device by means of DriveMonitor
(see also Section 15).
2
Switch off electronics power supply
3
Connect one COM port on the PC to
connector X300 on the converter
Cable order number: 6SX7005-0AB00
(see also Section 15.3)
4
Switch on electronics power supply AND press
down the UP key on the PMU of the
SIMOTRAS HD converter at the same time
The SIMOTRAS HD converter switches to
operating state o13.0
Note:
A software update can be started only from the
PMU panel and not
via an OP1S or the
DriveMonitor system
5
Open a DOS window on the PC and enter
program call:
HEXLOAD 7001Axxx.H86 7001Bxxx.H86 COMx
Start the program by pressing Return
The software update is performed
automatically
Note:
HEXLOAD.EXE: Loading program
7001Axxx.H86 and 7001Bxxx.H86:
Data files which contain the SIMOTRAS software
xxx is the SW release
COMx: COM1 or COM2
6
When the software has been updated
successfully, the SIMOTRAS HD switches
to operating state o13.2 for approx. 1 s
The SIMOTRAS HD converter then
switches to operating state o12.9 in many
cases (depending on which SW version
was previously installed in the converter)
for approximately 15s.
Note:
The currently programmed addressed is displayed
on the PMU while the update is in progress
The current status of the update routine is
displayed on the PC
7
Check the checksum:
Comparison of the value of parameter r062.001 with the checksum in the Internet under menu item
"Info" (see the inside page of the cover sheet of the operation instructions).
8
Was the electronics supply disconnected while
Step 6 was in progress?
?
yes
9b
Acknowledge any fault message that may
appear on the SIMOTRAS HD device
n
o
10b
Restore default setting
(see Section 7.4)
11b
Start up the converter again
(see Section 7.5)
Note:
The parameter set stored in Step 1 above can
be loaded from a PC or programming device
by means of DriveMonitor.
12
End