01.04 Maintenance
SIEMENS AG 6SG7000-0BA76 13-3
SIMOTRAS HD Operating Instructions
13.2 Replacement of components
13.2.1 Replacement of fan
WARNING
The converter fan may be replaced only by properly qualified personnel.
The snubber capacitors continue to carry hazardous voltage for up to 2 minutes after isolation
from the supply. For this reason, the converter must not be opened for at least two minutes
after switch-off.
Non-observance of the safety instructions can result in death, severe personal injury or
substantial property damage.
Replacement of fan on D400 / 98 – 180 Mre converters
2
1
4
3
The two fans are mounted on the underside of the converter.
• Remove connector
a.
• Release the two retaining clips
s on the fan and swing fan out downwards.
Installation:
• When mounting the fan make sure it is in the correct mounting position (blowing direction
upward, see arrow
d on the fan housing).
• Insert the fan into lugs
f and push upwards until it engages in retaining clips s
• Insert connector
a again.