01.04 Function descriptions
SIEMENS AG 6SG7000-0BA76 9-27
SIMOTRAS HD Operating Instructions
2)
Bus terminating
resistors deactivated
Bus terminating
resistors deactivated
Bus terminating
resistors activated
1)
Type of peer connection "Bus connection"
Up to 31 drives receive identical setpoints from a drive. The transmitting drive is selected with
"Enable transmit" = 1. "Enable transmit" must be = 0 for all other drives.
1) The interface cable shields should be connected at low impedance directly to the converters on the converter or
cabinet ground (e.g. using a clamp).
2) Twisted-pair cable, e.g. LIYCY 2x0.5 qmm; in the case of longer cable runs, an equipotential bonding conductor should
be used to ensure that the difference of the frame potentials between the connected units remains below 7V.
Rx
+
56
575859
-
-
+
+
6SG70
Rx
+
56575859
-
+
6SG70
Rx
+
56
57
58
59
-
++
6SG70
Rx
+
56575859
-
++
6SG70
10
Transmit
data
Enable
transmit=1
Bus terminating
resistors activated
Tx
-
+
10
Enable
transmit=0
Tx
10
Enable
transmit=0
Tx
10
Enable
transmit=0
Tx
-
-