01.04 Faults / alarms
SIEMENS AG 6SG7000-0BA76 10-3
SIMOTRAS HD Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
10.1.2.1 Supply faults
F001 Failure of electronics power supply
(active in all operating states)
Failure of the electronics supply voltage (terminals 5U1, 5W1, 5N1) in “RUN” state for longer than the “restart” time set in
parameter P086 or the electronics are operating on undervoltage.
Possible fault causes:
Line contactor has opened in “RUN” state
Brief supply failure
Supply voltage too low
Fault value: r047 Index 002 to 016:
1 Electronics supply voltage in “RUN” has been interrupted
for longer than setting in P086
i002 Duration of actual supply failure in 1/10 seconds
2 Supply failure prewarning responds periodically -
3 Supply failure prewarning is active for longer than 1.28 s -
F002 Anti-clockwise field on power connections (U1, V1, W1)
(active in all operating states)
F004 Phase failure on power connections (U1, V1, W1)
(active in operating states of o4)
The supply voltage RMS value, calculated from the area of each supply half-wave (rectified average value * peak factor), must
be greater than the response value for phase failure monitoring
100%
P353
P078.001
The distance between two identical supply zero passages of a phase must not exceed 450 degrees.
If one of these two conditions remains unfulfilled for longer than the “restart time” set in P086, a fault message is activated.
After switch-on, the converter waits in operating states o4 and o5 together for a period not exceeding the setting in P089 for
voltage to appear at the power terminals before activating the fault message.
Possible fault causes:
Parameter P353 is incorrectly set
Line contactor has opened in operation
Fuse has blown in incoming power section supply
Interruption in a thyristor firing pulse cable (auxiliary cathodes at connectors X12, X14, X16 are voltage carriers).
Fault value:
1 Voltage failure has occurred in supply (U1, V1, W1) (when P086=0)
2 Delay time set in parameter P089 has expired in operating state o4
3 Fuse has blown in power section
4 Voltage failure has lasted longer than period set in P086 (if this is >0)
5 2-phase current (e.g. because a phase is missing)
6 The "Main contactor checkback" (control word 2 bit 31) [see also P691] did not switch to "1" before the time set in P095
ran out, or switched back to "0" during operation [V1.8 and later].
F006 Undervoltage
(active in operating states of o4)
The voltage at terminals U1, V1 or W1 is lower than the response threshold for longer than the “restart time” set in P086.
Response threshold for supply voltage:
)
100%
P351
(1P078.001 +
Possible causes of fault
Line undervoltage
Monitoring values set too sensitively or incorrectly (P351, P078)