Faults / alarms 01.04
10-6 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
F016 Hardware fault on expansion board EB1
Fault value:
1 Fault on first EB1
2 Fault on second EB1
F017 Hardware fault on expansion board EB2
Fault value:
1 Fault on first EB2
2 Fault on second EB2
F018 Short circuit or overloading of binary outputs
(active in all operating states)
Possible causes of fault
Short circuit or overload at terminals 46, 48, 50 or 52 and 26 or 34
Fault value: r047 Index 002 to 016:
1 Short circuit or overload at binary outputs i002 Bit 8 = 1: Overload at terminal 46
Bit 9 = 1: Overload at terminal 48
Bit 10 = 1: Overload at terminal 50
Bit 11 = 1: Overload at terminal 52
Bit 12 = 1: Overload at terminal 26 (15 V output)
Bit 13 = 1: Overload at terminal 34, 44 or 210
(24 V output)
10.1.2.3 External faults, fault messages from free function blocks
Fault message from free function block FB286
(active in all operating states)
Fault value:
F019
1 the binector wired via parameter U100 Index.005 is in the state log.”1”
2 the binector wired via parameter U100 Index.006 is in the state log.”1”
3 the binector wired via parameter U100 Index.007 is in the state log.”1”
4 the binector wired via parameter U100 Index.008 is in the state log.”1”
Fault message from free function block FB287
(active in all operating states)
Fault value:
F020
1 the binector wired via parameter U101 Index.005 is in the state log.”1”
2 the binector wired via parameter U101 Index.006 is in the state log.”1”
3 the binector wired via parameter U101 Index.007 is in the state log.”1”
4 the binector wired via parameter U101 Index.008 is in the state log.”1”
F021 External fault 1
(active in all operating states)
Bit 15 control word 1 was in the log. "0" state for longer than the time set in P360 index 001.
F022 External fault 2
(active in all operating states)
Bit 26 control word 2 was in the log. "0" state for longer than the time set in P360 index 002.
Ramp-down monitoring, fault message from free function block FB2
(active in all operating states)
Fault value:
F023
1 The travel command has been cancelled but the minimum speed (P370) has not been reached within the period specified
in U441.
For further details, see the description of the crane control in Section 8, Sheet K15
2 the binector wired via parameter U100 Index.002 is in the state log.”1”
3 the binector wired via parameter U100 Index.003 is in the state log.”1”
4 the binector wired via parameter U100 Index.004 is in the state log.”1”