Faults / alarms 01.04
10-8 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
10.1.2.6 External faults
Fault message from free function block FB4
(active in all operating states)
Fault value:
F033
1 the binector wired via parameter U102 Index.001 is in the state log.”1”
2 the binector wired via parameter U102 Index.002 is in the state log.”1”
3 the binector wired via parameter U102 Index.003 is in the state log.”1”
4 the binector wired via parameter U102 Index.004 is in the state log.”1”
Fault message from free function block FB5
(active in all operating states)
Fault value:
F034
1 the binector wired via parameter U103 Index.001 is in the state log.”1”
2 the binector wired via parameter U103 Index.002 is in the state log.”1”
3 the binector wired via parameter U103 Index.003 is in the state log.”1”
4 the binector wired via parameter U103 Index.004 is in the state log.”1”
10.1.2.7 Drive faults
F035 Drive blocked
(active in operating states of – –, I, II)
The monitoring function responds if the following conditions are fulfilled for longer than the time set in parameter P355:
Positive or negative current limit reached
Stator current is greater than 1% of converter rated DC current
The actual speed value is less than 0.4% of maximum speed
Possible causes of fault
Drive blocked
F036 No stator current can flow
(active in operating states of – –, I, II)
This monitoring function responds if the firing angle is at 0° for more than 500 ms and the stator current is less than 1% of the
converter rated DC current.
Possible causes of fault
Break in motor cable
F037 I
2
t motor monitor has responded
(active in operating states of – –, I, II)
This monitoring function responds when an I
2
t value is reached which corresponds to the final temperature at 110% of the rated
motor current.
Possible causes of fault
Parameter P114 is incorrectly set
Drive has been operating for too long at >110% of rated motor current
F038 Overspeed
(active in operating states of – –, I, II)
This fault message is activated if the actual speed value (selected in P595) exceeds the positive (P380) or negative (P381)
threshold by 0.5%.
Possible causes of fault
Lower current limit has been input
Current-controlled operation
P512, P513 are set too low
Tachometer cable contact fault in operation close to maximum speed