Faults / alarms 01.04
10-10 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Fault Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
10.1.2.8 External faults
Fault message from free function block FB288
(active in all operating states)
Fault value:
F053
1 the binector wired via parameter U102 Index.005 is in the state log.”1”
2 the binector wired via parameter U102 Index.006 is in the state log.”1”
3 the binector wired via parameter U102 Index.007 is in the state log.”1”
4 the binector wired via parameter U102 Index.008 is in the state log.”1”
Fault message from free function block FB289
(active in all operating states)
Fault value:
F054
1 the binector wired via parameter U103 Index.005 is in the state log.”1”
2 the binector wired via parameter U103 Index.006 is in the state log.”1”
3 the binector wired via parameter U103 Index.007 is in the state log.”1”
4 the binector wired via parameter U103 Index.008 is in the state log.”1”
10.1.2.9 Start-up faults
F056 Important parameter is not set
(active in operating states of o6)
This fault message is activated if certain parameters are still set to 0.
Fault value:
1 Speed controller actual value selection in P083 is still set to 0
2 Rated motor current in P100 is still set to 0.0
F058 Parameter settings are not consistent
(active in operating states of o6)
Inconsistent values have been set in mutually dependent parameters.
Fault value:
4 The first threshold for P gain adaptation of the speed controller set in parameter P556 is higher than the second threshold
setting in parameter P559
5 P557 is set to greater than P560
6 P558 is set to greater than P561
7 If P083=1 (analog tachometer), then P746 may not equal 0 (main actual value is not connected)
8 If P083=2 (pulse encoder), then P140 may not equal x0 (no pulse encoder installed)
10 P090 (stabilization time for supply voltage) >
P086 (time for automatic restart)
11 P090 (stabilization time for supply voltage) >
P089 (waiting time in state o4 or o5)
12 P445=1 is set (switch-on, shutdown and crawl act as a pushbutton) although no binector is parameterized as a shutdown
button (P444=0)
14 Parameter U673 > U674 (this setting is not permitted; see function diagram B152)