01.04 Parameter list
SIEMENS AG 6SG7000-0BA76 11-55
SIMOTRAS HD Operating Instructions
PNU Description Value range
[Unit]
No. indices See
Change
P698
*
BDS
(G152)
Source for selection of enabling command for speed-dependent
speed controller PI / P function switchover
Selection of binector to control enabling of the speed-dependent PI / P
controller switchover function (see also P222
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
11.35 Analog inputs (main actual value, main setpoint, selectable inputs)
(see also Section 8, Sheets G113 and G114)
Analog input terminals 4 / 5 (main setpoint)
P700
*
(G113)
Signal type of "Main setpoint" analog input
0 = Voltage input 0 to ±10 V
1 = Current input 0 to ±20 mA
2 = Current input 4 to 20 mA
0 to 2
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P701
FDS
(G113)
Normalization of "Main setpoint" analog input
This parameter specifies the percentage value which is generated for an
input voltage of 10V (or an input current of 20mA) at the analog input.
The following general rule applies:
With a voltage input:
PV
Y
X
701 10[%] =∗ X .. Input voltage in volts
Y .. % value which is generated for input
current X
With a current input:
PmA
Y
X
701 20[%] =∗ X .. Input current in mA
Y .. % value which is generated for input
current X
-1000.0 to 1000.0
[%]
0.1%
Ind: 4
FS=100.0
Type: I2
P052 = 3
P051 = 40
Online
P702
(G113)
Offset for "Main setpoint" analog input
-200.00 to 199.99
[%]
0.01%
Ind: None
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P703
*
(G113)
Mode of signal injection at "Main setpoint" analog input
0 = Injection of signal with sign
1 = Injection of absolute value of signal
2 = Injection of signal with sign, inverted
3 = Injection of absolute value of signal, inverted
0 to 3
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P704
*
(G113)
Source for selection of sign reversal at "Main setpoint" analog input
Selected binector in “1” state = sign reversal
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
P705
(G113)
Filtering time for "Main setpoint" analog input
Note: Hardware filtering of approximately 1 ms is applied as standard
0 to 10000
[ms]
1ms
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P706
*
(G113)
Source for enabling of "Main setpoint" analog input
Selected binector in “1” state = enabled
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: None
FS=1
Type: L2
P052 = 3
P051 = 40
Offline