EasyManua.ls Logo

Siemens Sinamics G120 CU240S DP - Page 194

Siemens Sinamics G120 CU240S DP
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.11 Operation in fieldbus systems
Frequency inverter
194 Operating Instructions, 08.10. 2008, t.b.d.
Figure 5-38 Function block for reading parameters
You first have to define how many parameters (MB62), which parameter numbers (MW50,
MW52, etc.), and how many parameter indices (MW58, MB59, etc.) are read for each
parameter number. The specifications are saved in DB1.
SFC 58 copies the specifications for the parameters to be read from DB1 and sends them to
the frequency inverter as a read request. No other read requests are permitted while this one
is being processed.

Table of Contents

Related product manuals