Technical data
8.4 Technical data, PM240 Power Modules
Frequency inverter
228 Operating Instructions, 08.10. 2008, t.b.d.
Table 8- 3 PM240 Frame Size D and E
Order No., unfiltered 6SL3224-0BE31-
5AA0
6SL3224-0BE31-
8AA0
6SL3224-0BE32-
2AA0
6SL3224-0BE33-
0AA0
6SL3224-0BE33-
7AA0
Order No., filtered 6SL3224-0BE31-
5UA0
6SL3224-0BE31-
8UA0
6SL3224-0BE32-
2UA0
6SL3224-0BE33-
0UA0
6SL3224-0BE33-
7UA0
Power rating for HO
base load
15 kW / 20 PS 18.5 kW / 25 PS 22 kW / 30 PS 30 kW / 40 PS 37 kW / 50 PS
Input current for HO
base load
40 A 46 A 56 A 73 A 90 A
Output current for
HO base load
32 A 38 A 45 A 60 A 75 A
Input current for LO
base load
46 A 53 A 72 A 88 A 105 A
Output current for LO
base load
38 A 45 A 60 A 75 A 90 A
Fuse 50 A 63 A 80 A 100 A 125 A
Heat loss 0.44 KW 0.55 KW 0.72 KW 1.04 KW 1.2 KW
Cooling air
requirement
55 l/s / 120 CFM 55 l/s / 120 CFM 55 l/s / 120 CFM 110 l/s / 240 CFM 110 l/s / 240 CFM
Cable cross-section
for line and motor
connections
10 … 35 mm
2
7 … 2 AWG
10 … 35 mm
2
7 … 2 AWG
10 … 35 mm
2
7 … 2 AWG
25 … 35 mm
2
3 … 2 AWG
25 … 35 mm
2
3 … 2 AWG
Weight Filtered: 16 kg /
35 lb; unfiltered:
13 kg / 29 lb
Filtered: 16 kg /
35 lb; unfiltered:
13 kg / 29 lb
Filtered: 16 kg /
35 lb; unfiltered:
13 kg / 29 lb
Filtered: 23 kg /
51 lb; unfiltered:
16 kg / 35 lb
Filtered: 23 kg /
51 lb; unfiltered:
16 kg / 35 lb