Commissioning
4.4 Commissioning with factory settings
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
55
Table 4- 2 Factory setting of additional important parameters
Parameter Factory setting Meaning of the factory setting Function Access
level
P0003 1 Access to the most frequently
used parameters
Selecting the user access level 1
P0004 0 All parameters are displayed Parameter filter: filters parameters in
accordance with the functionality
1
P0010 0 Ready to be entered Commissioning parameter 1
P0100 0 Europe [50 Hz] Frequency of the regional supply network
IEC, Europe
NEMA, North America
1
P0300 1 Induction motor Select the motor type (induction motors /
synchronous motor)
2
P0304 400 [V] Rated motor voltage
(in accordance with rating plate in V)
1
P0305 depends on the
Power Module
[A] Rated motor current
(in accordance with rating plate in A)
1
P0307 depends on the
Power Module
[kW/hp] Rated motor output
(in accordance with the rating plate in kW/hp)
1
P0308 0 [cos phi] Rated motor power factor (in accordance with
rating plate in cos 'phi') when P0100 = 1.2,
then P0308 is irrelevant
1
P0309 0 [%] Rated motor efficiency (in accordance with
rating plate in %) when P0100 = 0, then
P0309 is irrelevant
1
P0310 50 [Hz] Rated motor frequency
(in accordance with rating plate in Hz)
1
P0311 1395 [rpm] Rated motor speed
(in accordance with rating plate in rpm)
1
P0335 0 Non-ventilated: Shaft-mounted
fan in the motor
Motor cooling (specify the motor cooling
system)
2
P0625 20 °C Ambient temperature of motor 3
P0640 200 [%] Motor overload factor (entered in % referred
to P0305)
2
P0700 2 or 6 6 for bus-capable CUs
2 for stand-alone CUs
Select the command source 1
P0727 0 DI0: On / off
DI1: Direction reversal
Control response when the motor starts (start,
stop, reverse)
3
P0970 0 Blocked Restore factory settings 1
P1000 2 or 6 6 for bus-capable CUs
2 for stand-alone CUs
Select the source of the frequency setpoint
(setpoint input)
1
P1080 0 [Hz] Minimum frequency 1
P1082 50 [Hz] Maximum frequency 1
P1120 10 [s] Ramp-up time 1
P1121 10 [s] Ramp-down time 1
P1300 0 V/f control with linear
characteristic
Control mode 2
P3900 0 No quick commissioning Completes the quick commissioning. 1