Commissioning
4.4 Commissioning with factory settings
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
57
Analog inputs
Terminal Abbreviation Parameter Factory setting Meaning of the factory setting
3 AI0+
4 AI0-
AI0 P0756 [0] 0 Set unipolar voltage input
0 V … +10 V DC
in addition to parameterizing DIP switch on CU housing.
10 AI1+
11 AI1-
AI1 P0756 [1] 0 Set unipolar voltage input
0 V … +10 V DC
in addition to parameterizing DIP switch on CU housing.
Analog outputs
Terminal Abbreviation Parameter Factory setting Meaning of the factory setting
12 AO0+
13 AO0-
AO0 P0771[0] 21 Frequency on the inverter output;
analog output 0 can be switched from current output to
voltage output by means of P0776
26 AO1+
27 AO1-
AO1 P0771[1] 21 Frequency on the inverter output;
analog output 1 is current output only
Encoder interface (encoder)
Terminal Function Parameter Factory setting Meaning of the factory setting
70 Channel A -
non-inverting
71 Channel A -
inverting
72 Channel B -
non-inverting
73 Channel B -
inverting
74 Zero pulse -
non-inverting
75 Zero pulse -
inverting
P0400 0 Evaluation of the speed encoder is blocked
PTC/KTY84 interface
Terminal Abbreviation Parameter Factory setting Meaning of the factory setting
14 PTC+
15 PTC-
P0601 0 Evaluation of the motor temperature sensor is blocked