Commissioning
4.6 Commissioning with the operator panel
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
75
Table 4- 7 Motor data in accordance with the specifications on the motor rating plate
Parameter Description
P0304 = … Rated motor voltage (enter value as specified on the motor rating plate in Volt)
400 [v] (factory setting)
The rating plate data entered must correspond to the motor connection type
(star/delta) (i.e. with a delta motor connection, the delta rating plate data must be
entered).
P0305 = … Rated motor current (enter value as specified on the motor rating plate in Ampere)
1 [A] (factory setting)
P0307 = … Rated motor power (enter value as specified on the motor rating plate in kW or hp)
0.37 [kW / hp] (factory setting)
If P0100 = 0 or 2, the data is specified in kW
If P0100 = 1, the data is specified in hp.
P0308 = ... Rated motor power factor [cos phi]
0.820 (factory setting)
This parameter is irrelevant when P0100 = 1 or 2.
P0310 = … Rated motor frequency (enter value as specified on the motor rating plate in Hz)
50.00 [Hz] (factory setting)
When this parameter is changed, the number of pole pairs for the motor is
automatically recalculated.
P0311 = … Rated motor speed (enter value as specified on the motor rating plate in rpm)
1395 [U / min]
Table 4- 8 Specify command source and frequency setpoint source
Parameter Description
P0700 = 2 or
6
Select the command source
0: factory setting (restores factory settings for CU)
1: BOP (Basic Operator Panel keys)
2: Digital inputs (factory setting for 'stand-alone' CUs)
4: USS on RS 232
5: USS on RS 485
6: Fieldbus (factory setting for fieldbus-capable CUs)
P1000 = 2 or
6
Select the setpoint source
0: No main setpoint
1: MOP setpoint
2: Analog setpoint (factory setting for stand-alone CUs)
3: Fixed frequency
4: USS on RS 232
5: USS on RS 485
6: Fieldbus (factory setting for fieldbus-capable CUs)
7: Analog setpoint 2