Communication via RS485
5.3 Communication via USS
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
119
Write the parameter number into the PNU (PKE bit 10 ... 0).
≥ 2000
- offset.
Write the parameter number minus the offset into the PNU
(PKE bit
10 … 0).
Write the offset in the page index (IND bit 15 … 8).
Table 5- 7 Offset and page index of the parameter numbers
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 7 … 0).
Parameter contents can be parameter values or connector parameters. You require two
words for connector parameters. You can find more information on interconnecting
connector parameters in the operating instructions of the Control Unit in the section
"Interconnecting signals in the inverter".
Enter the parameter value in the parameter channel right-justified as follows:
8-bit values:
… 15 are zero.
16-bit values:
32-bit values:
Enter a connector parameter right-justified as follows:
Number of the connector parameter:
Drive object of the connector parameter:
The index or bit field number of the connector parameter: