Communication via RS485
5.6 Communication via P1 - only CU230P-2 HVAC, CU230P-2 BT
Fieldbuses
164 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
5.6.2
Setting the address
Valid address area: 1 … 99
You have the following options for setting the address:
Using the address switch on the Control Unit:
Figure 5-13 Address switch with example for bus address 10
The address switch has priority over the other settings.
Using Startdrive or an operator panel via parameter p2021 (default setting: p2021 = 99).
It is only possible to change p2021 if an invalid address is set in the address switch.
If you are working with Startdrive, back up the settings so they are not lost if the power
fails.
You can find the position of the address switch in the operating instructions for the inverter.
Manuals and technical support (Page 232)
Activating the changed bus address
Procedure
1. Set the address as described above.
2. Switch off the inverter power supply.
3. Wait until all LEDs on the inverter are dark.
4. Switch on the inverter power supply again.
Your settings become effective after switching on.
You have now set the bus address.

Table of Contents

Other manuals for Siemens SINAMICS G120P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120P and is the answer not in the manual?

Siemens SINAMICS G120P Specifications

General IconGeneral
Frequency Range0 Hz to 550 Hz
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V, 380 V to 480 V, 500 V to 690 V
Output Voltage0V to input voltage
Control TypeVector control, V/f control
Protection ClassIP20, IP55
Communication InterfacesPROFIBUS, PROFINET, Modbus RTU
Cooling MethodAir cooling
AltitudeUp to 2000 m without derating
Power Range0.37 to 630 kW

Related product manuals