Communication via EtherNet/IP
4.4 Configuring communication via EtherNet/IP
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
87
4.4.2
Special issues if you wish to use the ODVA AC/DC Drive profile
If you change the following parameters using Startdrive or an operator panel, you must
switch off the inverter power supply and switch it on again in order for the changes to
become effective.
Setting the off response for the motor
You set the standard off response for the inverter using parameter p8981:
p8981 = 0: OFF1 (factory setting), also corresponds to the setting in the SINAMICS
profile
p8981 = 1: OFF2
You can find details about OFF1 and OFF2 in the operating instructions of the Control Unit in
the Section "Switching on and switching off a motor".
Setting the speed and torque scaling
You scale the speed and torque display using parameter p8982 or p8983. Setting range: 2
5
to 2
-5
.
Displaying the maximum process data that can be transferred (PZD)
r2067[0] maximum interconnected PZD length - receiving
r2067[1] maximum interconnected PZD length - sending
Switching over the master control from the controller to Startdrive
In order to retrieve the master control using Startdrive, you must either switch the CPU to
STOP, or interrupt the connection to the controller.

Table of Contents

Other manuals for Siemens SINAMICS G120P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120P and is the answer not in the manual?

Siemens SINAMICS G120P Specifications

General IconGeneral
Frequency Range0 Hz to 550 Hz
Ambient Temperature-10°C to +50°C
Storage Temperature-40°C to +70°C
Relative Humidity5% to 95% (non-condensing)
Voltage Range200 V to 240 V, 380 V to 480 V, 500 V to 690 V
Output Voltage0V to input voltage
Control TypeVector control, V/f control
Protection ClassIP20, IP55
Communication InterfacesPROFIBUS, PROFINET, Modbus RTU
Cooling MethodAir cooling
AltitudeUp to 2000 m without derating
Power Range0.37 to 630 kW

Related product manuals