Communication via PROFIBUS and PROFINET
3.6 Communication via PROFINET
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
67
Settings and displays for PROFIenergy in the inverter
Pause time
● Minimum pause time: p5602
– When the pause time, which is sent using command "Start_Pause", is equal to or
greater than the value in p5602[1], then the inverter goes into the energy-saving
mode.
– When the pause time is less than p5602[1], the inverter rejects the command
"Start_Pause" with 50 hex (no appropriate pause mode).
● Maximum pause time: p5606
If you set p5611.0 = 1, you block the response of the inverter to PROFIenergy control
commands. In this case, the inverter rejects the "Start_Pause" command with 50 hex (no
appropriate pause mode).
Transition into the energy-saving mode from the PROFIdrive states ready (S3) and operation (S4)
If you set p5611.2 = 1, you allow the transition into the energy-saving mode from the
PROFIdrive states ready (S3) and operation (S4).
To do so, you must set one of the following settings:
● p5611.1 = 1: With the transition to the energy-saving mode, the inverter issues an OFF1
command and enters the start-inhibit state (S1).
● p5611.1 = 0: You can use p5614 to interconnect a signal source that switches the inverter
off and places it in the start inhibited state (S1).
If the control sends the command "End_Pause" or "Start_Pause" with a pause time of 0, then
the inverter does not restart, even if the appropriate enable signals are still set.
An OFF1/on command is required in order that the inverter restarts.
PROFIenergy measured values
SINAMICS source parameters
166 Power factor 1 12 1 r0038 Smoothed power factor 0 … 1