Communication via PROFIBUS and PROFINET
3.1 PROFIDRIVE profile - Cyclic communication
Fieldbuses
26 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Control and status word 3
Control word 3 is preassigned as follows:
● Bits 0 … 15 manufacturer-specific
Status word 3 is preassigned as follows:
● Bits 0 … 15 manufacturer-specific
Signal interconnection
in the inverter
1)
0 1 = fixed setpoint bit 0 Selects up to 16 different fixed
setpoints.
p1020[0] = r2093.0
Changes over between settings
for different motors (drive data
5 1 = DDS selection bit 1 p0821 = r2093.5
1 = technology controller enable
11 1 = Enable droop Enable or inhibit speed control-
p1492[0] = r2093.11
12 1 = torque control active
Changes over the control mode
for vector control.
p1501[0] = r2093.12
13 1 = no external fault
0 = external fault is active (F07860)
-- p2106[0] = r2093.13
15 1 = CDS bit 1 Changes over between settings
for different operation interfaces
p0811[0] = r2093.15
If you switch from telegram 350 to a different one, then the inverter sets all interconnections
p1020, … to "0". Exception: p2106 = 1.