Communication via AS-i - only for G110M
7.4 Assignment tables
Fieldbuses
224 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
7.4
Assignment tables
Fixed speeds - Single Slave
Table 7- 2 Fixed speeds via the motor control bits
AS-i.DO3
AS-i.DO2
AS-i.DO1
AS-i.DO0
Response in the inverter
0
0
0
0
OFF1
0 0 0 1 On + fixed speed 1 (factory setting: 1500 rpm)
0
0
1
0
On + fixed speed 2 (factory setting: -1500 rpm)
0
0
1
1
On + fixed speed 3 (factory setting: 300 rpm)
0
1
0
0
On + fixed speed 4 (factory setting: 450 rpm)
0
1
0
1
On + fixed speed 5 (factory setting: 600 rpm)
0
1
1
0
On + fixed speed 6 (factory setting: 750 rpm)
0
1
1
1
On + fixed speed 7 (factory setting: 900 rpm)
1
0
0
0
On + fixed speed 8 (factory setting: 1050 rpm)
1
0
0
1
On + fixed speed 9 (factory setting: 1200 rpm)
1
0
1
0
On + fixed speed 10 (factory setting: 1350 rpm)
1
0
1
1
On + fixed speed 11 (factory setting: 1500 rpm)
1
1
0
0
On + fixed speed 12 (factory setting: 1650 rpm)
1
1
0
1
On + fixed speed 13 (factory setting: 1800 rpm)
1
1
1
0
On + fixed speed 14 (factory setting: 1950 rpm)
1
1
1
1
Acknowledge fault or OFF2
Modified addressing - scaling factors
Table 7- 3 Scaling of the speed setpoint via AS-i.P0 … AS-i.P3
AS-i.P3
AS-i.P2
AS-i.P1
AS-i.P0
Scaling factor
Frequency (Hz)
1
1
1
1
1
50
1
1
1
0
0.9
45
1
1
0
1
0.8
40
1
1
0
0
0.7
35
1
0
1
1
0.6
30
1
0
1
0
0.5
25
1 0 0 1 0.45 22.5
1
0
0
0
0.4
20
0 1 1 1 0.35 17.5
0
1
1
0
0.3
15
0
1
0
1
0.25
12.5
0
1
0
0
0.2
10
0
0
1
1
0.15
7.5
0
0
1
0
0.1
5
0
0
0
1
0.07
3.5
0
0
0
0
0.05
2.5