Communication via PROFIBUS and PROFINET
3.1 PROFIDRIVE profile - Cyclic communication
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
25
Control and status word 2
Control word 2 is preassigned as follows:
● Bits 0 … 11 manufacturer-specific
● Bits 12 … 15 corresponding to the PROFIdrive profile
Status word 2 is preassigned as follows:
● Bits 0 … 11 manufacturer-specific
● Bits 12 … 15 corresponding to the PROFIdrive profile
Signal interconnection in the
inverter
1 = drive data set selection DDS bit 0
1 = drive data set selection DDS bit 1
2…6 Reserved
1 = parking axis is selected
8 1 = travel to fixed stop
Reserved p1545[0] = r2093.8
1 = master sign-of-life bit 0
p2045 = r2050[3]
1 = master sign-of-life bit 1
1 = master sign-of-life bit 3
1 = master sign-of-life bit 4
Signal interconnection in the
inverter
1 = Drive data set DDS effective, bit 0
1 = Drive data set DDS effective, bit 1
1 = travel to fixed stop active
Internally interconnected
13 Slave sign of life bit 1
15 Slave sign of life bit 3