Communication via PROFIBUS and PROFINET
3.1 PROFIDRIVE profile - Cyclic communication
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
27
Status word 3 (ZSW3)
Bit
Meaning
Description
Signal intercon-
nection in the
inverter
0
1 = DC braking active
--
p2051[3] = r0053
1 1 = |n_act | > p1226 Absolute current speed > stationary
state detection
2 1 = |n_act | > p1080 Absolute actual speed > minimum
speed
3 1 = i_act ≧ p2170 Actual current ≥ current threshold
value
4 1 = |n_act | > p2155 Absolute actual speed > speed
threshold value 2
5 1 = |n_act | ≦ p2155 Absolute actual speed < speed
threshold value 2
6
1 = |n_act | ≧ r1119
Speed setpoint reached
7 1 = DC link voltage ≦ p2172 Actual DC link voltage ≦ threshold
value
8 1 = DC link voltage > p2172 Actual DC link voltage > threshold
value
9 1 = ramp-up or ramp-down complet-
ed
Ramp-function generator is not
active.
10 1 = technology controller output at
the lower limit
Technology controller output ≦
p2292
11 1 = technology controller output at
the upper limit
Technology controller out-
put > p2291
12 Not used
13
Not used
14 Not used
15
Not used