Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
152 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
The inverter can simultaneously process up to 32 SubscribeCOV services. These can all
refer to the same object instances - or different object instances.
SubscribeCOV monitors the property changes of the following objects:
● Analog Input (AIxx),
● Analog Output (AOxx),
● Analog Value (AVxx),
● Binary Value (BVxx) and
● Multi-state Input (MSIxx)
Note
SubscribeCOV services are not retentive; i.e., when restarting the CU the master must
reinitiate SubscribeCOV
services.
Code numbers of the object types supported in BACnet
Code number for BACnet
object type
Code number for BACnet
object type
Object properties of the "Device" object type
• Object_Identifier • Application_Software_Version • APDU_Timeout
• Object_Name • Protocol_Version • Number_Of_APDU_Retries
• Object_Type • Protocol_Revision • Max Master
• System_Status • Protocol_Services_Supported • Max Info Frames
• Vendor_Name • Protocol_Object_Types_Supported • Device Address Binding
• Vendor_Identifier • Object_List • Database Revision
• Model_Name • Max_APDU_Length_Accepted
1)
• Firmware_Revision • Segmentation_Supported
2)
2)