Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
154 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Text active /
text inactive
BI1 DI1 ACT State of DI 1 ON/OFF ON/OFF R r0722.1
BI3 DI3 ACT State of DI 3 ON/OFF ON/OFF R r0722.3
State of AI 1 - used as DI
State of AI 2 - used as DI
Text active /
text inactive
BV0 RUN / STOP
Inverter status regardless of com-
RUN / STOP STOP RUN R r0052.2
BV1 FWD / REV Direction of rotation regardless of
REV / FWD FWD REV R r0052.14
BV4 MANUAL /
AUTO ACT
Indicates the source of the manu-
al/auto inverter control
AUTO /
MANUAL
AUTO LOCAL R r0052.9
BV7 CTL
OVERRIDE
ACT
ACT displays the inverter's control
unit from the BACnet override con-
trol unit via BV93.
Note that the operator panel's
"Manual" operating mode has a
higher priority than the BACnet
ON/OFF 0 1 R r2032[10]