Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
161
If the response is still not available, then you receive the following message via the present
value window of the OSV1:
Table 5- 35 Read parameter content via OSV1
Byte
Description
2F h
00 h
0004 h
1
2
3,4
Function code 2F h (47)
Response length 0 (error)
Error code 4 h (response still not available)
If you wish to read the response once more, then you obtain the following message via the
present value window of the OSV1:
Table 5- 36 Read parameter content again via OSV1
Byte
Description
2F h
00 h
0002 h
1
2
3,4
Function code 2F h (47)
response length 0 (error)
Error code 2 h (Invalid State)
Overview of the error codes
1 h: Invalid Length (invalid length)
2 h: Invalid State (action is not permitted in the actual inverter state)
3 h: Invalid function Code (FC = 2 hex)
4 h: Response not ready (the response has still not been issued)
5 h: Internal Error (general system error)
Incorrect access operations to parameters via data set 47 are logged in objects OSV0 and
OSV1.