Communication via AS-i - only for G110M
7.2 Single Slave mode
Fieldbuses
220 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
Default setting 32: Modified Single Slave mode
In Single Slave mode with modified addressing the control specifies the following:
AS-i.DO0
>
AS-i.DO1
>
-clockwise / OFF 1
AS-i.DO2
>
Speed via potentiometer or AI0
AS-i.DO3
>
= 2093.3
= 2093.3
Acknowledge errors with a positive edge
enable, if p2093.3 = 1
The inverter sends as response:
p2080[0] = 899.0
>
-i.DI0
p2080[1] = 807.0
>
-i.DI1
p2080[2] = 722.0
>
-i.DI2
p2080[3] = 722.1
>
-i.DI3
If an alarm or fault is pending in the inverter, it sends a warning or fault message.
Table 7-5 Alarm and fault messages via RP0 … RP3 from the inverter to the AS-i
master (Page 225).
Scaling factors for the speed
The scaling factor is specified via AS-i.P0 … AS-i.P3. A diagnostic request is also performed
when AS-i.P0 is sent.
This means, if the control specifies a scaling factor and an alarm or fault is pending in the
inverter, it sends the current alarm or fault messages and accepts simultaneously the sent
value consisting of AS-i.P0 … AS-i.P3 as new scaling factor.
AS-i.P0
AS-i.P1
AS-i.P2
AS-i.P3
Table 7-3 Scaling of the speed setpoint via AS-i.P0 … AS-i.P3 (Page 224).