Communication via PROFIBUS and PROFINET
3.1 PROFIDRIVE profile - Cyclic communication
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
37
Table 3- 5 Error numbers for response identifier 7
Illegal parameter number (access to a parameter that does not exist)
01 hex
Parameter value cannot be changed
(change request for
a parameter value that cannot be
changed)
Lower or upper value limit exceeded (change request with a value outside the value limits)
03 hex
(access to a subindex that does not exist)
No array (access with a subindex to non-indexed parameters)
05 hex
(change request with a value that does not match the data type of the
06 hex
Setting not permitted, only resetting
(change request with a value not equal to 0 without
07 hex
Descriptive element cannot be changed
(change request to a descriptive element error
value that cannot be changed)
No master control (change request but with no master control, see also p0927.)
11 hex
Request cannot be executed due to the operating state
(access is not possible for tempo-
rary reasons that are not specified)
14 hex
(change request with a value that is within the limits but which is illegal
for other permanent reasons, i.e. a parameter with defined individual values)
Parameter number is currently deactivated (depending on the mode of the inverter)
Channel width is insufficient (communication channel is too small for response)
68 hex
(parameter can only assume certain values)
6A hex
Request not included / task is not supported
(the valid request identifications can be found
in table "Request identifications controller → inverter")
6B hex
No change access for a controller that is enabled
. (The operating state of the inverter
prevents a parameter change)
86 hex
Write access only for commissioning (p0010 = 15) (operating state of the inverter prevents
a parameter change)
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit
(change request to a value that lies within
the "absolute" limits, but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit
(example: a parameter value is too large for
CC hex
Change request not permitted
(change is not permitted as the access code is not availa-