Communication via PROFIBUS and PROFINET
3.2 PROFIDRIVE profile - Acyclic communication
Fieldbuses
46 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
18 hex
Number of values not consistent
(number of values of the parameter data to not match the number of elements
in the parameter address)
Drive object does not exist (access to a drive object that does not exist)
Parameter text cannot be changed
21 hex
(illegal or not support request ID).
6B hex
A change request for a controller that has been enabled is not possible
. (The inverter rejects the change re-
quest because the motor is switched on. Please observe the "Can be changed" parameter attribute (C1, C2, U,
T) in the List Manual.
Manuals and technical support (Page 232))
Change request is only possible when the motor is being commissioned (p0010 = 3).
Change request is only possible when the power unit is being commissioned (p0010 = 2).
70 hex
Change request is only possible for quick commissioning (basic commissioning) (p0010 = 1).
Change request is only possible if the inverter is ready (p0010 = 0).
Change request is only possible for a parameter reset (restore to factory setting) (p0010 = 30).
Change request possible only during commissioning of the safety functions (p0010 = 95).
Change request is only possible when a technological application/unit is being commissioned (p0010 = 5).
Change request is only possible in a commissioning state (p0010 ≠ 0).
Change request is not possible for internal reasons (p0010 = 29).
Change request is not possible during download.
Change request is not possible during download.
Accepting the master control is inhibited via BI: p0806.
83 hex
Desired interconnection is not possible
(the connector output does not supply a float value although the con-
nector input requires a float value)
84 hex
Inverter does not accept a change request
(inverter is busy with internal calculations. See parameter r3996 in
the inverter List Manual.
Manuals and technical support (Page 232))
No access methods defined.
86 hex
Write access only during commissioning of the data records (p0010 = 15)
(operating status of the inverter pre-
vents a parameter change.)
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit
(change request to a value that lies within the "absolute" limits,
but is however below the currently valid lower limit)
Change request above the currently valid limit(example: a parameter value is too large for the inverter power)
Change request not permitted (change is not permitted as the access code is not available)