Introduction
1.3 Characteristics
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
29
Monitoring Functions
Availability of the device is greatly increased because of self-monitoring of the internal measurement circuits,
power supply, hardware, and software;
Current transformer and voltage transformer secondary circuits are monitored using summation and sym-
metry check techniques
Trip circuit monitoring;
Phase rotation check.
Ground Fault Detection 50N(s), 51N(s), 67N(s), 59N/64
Displacement voltage is measured or calculated from the three phase voltages;
Determination of a faulty phase on ungrounded or grounded networks;
Two-element Ground Fault Detection: 50Ns-1 and 50Ns-2;
High sensitivity (as low as 1 mA);
Overcurrent element with definite time or inverse time delay;
one user-defined, two logarithmic inverse current/time elements and one V0-I0-ϕ characteristic for 51 and
51N are available;
Direction determination with zero-sequence quantities (I
0
, V
0
), wattmetric ground fault direction determina-
tion;
Any element can be set as directional or non-directional — forward sensing directional, or reverse sensing
directional;
Directional characteristic can be adjustable;
Optionally applicable as additional ground fault protection.
Intermittent Ground Fault Protection
Detects and accumulates intermittent ground faults;
Tripping after configurable total time.
Automatic Reclosing 79
Single-shot or multi-shot;
With separate dead times for the first and all succeeding shots;
Protective elements that initiate automatic reclosing are selectable. The choices can be different for phase
faults and ground faults;
Different programs for phase and ground faults;
Interaction to time overcurrent protection element and ground fault elements. They can be blocked in de-
pendence of the reclosing cycle or released instantaneously;
Synchronous reclosing is possible (only for 7SJ623, 7SJ624 and 7SJ64) in combination with the integrated
synchronizing feature.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals