Introduction
1.3 Characteristics
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
30
Fault Location
Initiation by trip command, external command or dropout of pickup;
Fault distance is calculated and the fault location given in ohms (primary and secondary) and in kilometers
or miles;
up to three line sections can be configured.
Breaker Failure Protection 50 BF
Checking current flow and/or evaluation of the circuit breaker auxiliary contacts;
Initiated by the tripping of any integrated protective element that trips the circuit breaker;
Initiation possible via a binary input from an external protective device.
Flexible Protective Functions
Up to 20 protection functions which can be set individually to operate in three-phase or single-phase mode;
Any calculated or directly measured value can be evaluated on principle;
Standard protection logic function with definite time characteristic;
Internal and configurable pickup and dropout delay;
Modifiable message texts.
Synchrocheck (only 7SJ623, 7SJ624 and 7SJ64)
Verification of the synchronous conditions before reclosing after three-pole tripping;
Fast measurement of the voltage difference V, the phase angle difference ∆ϕ and the frequency difference
f;
Alternatively, check of the de-energized state before reclosing;
Switching possible for asynchronous system conditions with prediction of the synchronization time (only
7SJ64);
Settable minimum and maximum voltage;
Verification of the synchronous conditions or de-energized state also possible before the manual closing of
the circuit breaker, with separate limit values;
Measurement also possible via transformer without external intermediate matching transformer;
Measuring voltages optionally phase–to–phase or phase–to–ground.
RTD-Boxes
Detection of any ambient temperatures or coolant temperatures by means of RTD-Boxes and external tem-
perature sensors.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals