Appendix
A.9 Information List
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
671
2632 Phase A reverse (Phase A re-
verse)
67 Direct. O/C OUT on * * LED BO 63 84 1 Yes
2633 Phase B reverse (Phase B re-
verse)
67 Direct. O/C OUT on * * LED BO 63 85 1 Yes
2634 Phase C reverse (Phase C re-
verse)
67 Direct. O/C OUT on * * LED BO 63 86 1 Yes
2635 Ground forward (Ground forward) 67 Direct. O/C OUT on * * LED BO 63 87 1 Yes
2636 Ground reverse (Ground reverse) 67 Direct. O/C OUT on * * LED BO 63 88 1 Yes
2637 67-1 is BLOCKED (67-1
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 91 1 Yes
2642 67-2 picked up (67-2 picked up) 67 Direct. O/C OUT * On
Off
* LED BO 63 67 2 Yes
2646 67N-2 picked up (67N-2 picked
up)
67 Direct. O/C OUT * On
Off
* LED BO 63 62 2 Yes
2647 67-2 Time Out (67-2 Time Out) 67 Direct. O/C OUT * * * LED BO 63 71 2 Yes
2648 67N-2 Time Out (67N-2 Time
Out)
67 Direct. O/C OUT * * * LED BO 63 63 2 Yes
2649 67-2 TRIP (67-2 TRIP) 67 Direct. O/C OUT * on m LED BO 63 72 2 Yes
2651 67/67-TOC switched OFF (67/67-
TOC OFF)
67 Direct. O/C OUT On
Off
**LEDBO63101Yes
2652 67/67-TOC is BLOCKED (67
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 11 1 Yes
2653 67/67-TOC is ACTIVE (67
ACTIVE)
67 Direct. O/C OUT On
Off
**LEDBO63121Yes
2655 67-2 is BLOCKED (67-2
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 92 1 Yes
2656 67N/67N-TOC switched OFF
(67N OFF)
67 Direct. O/C OUT On
Off
**LEDBO63131Yes
2657 67N/67N-TOC is BLOCKED
(67N BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 14 1 Yes
2658 67N/67N-TOC is ACTIVE (67N
ACTIVE)
67 Direct. O/C OUT On
Off
**LEDBO63151Yes
2659 67N-1 is BLOCKED (67N-1
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 93 1 Yes
2660 67-1 picked up (67-1 picked up) 67 Direct. O/C OUT * On
Off
* LED BO 63 20 2 Yes
2664 67-1 Time Out (67-1 Time Out) 67 Direct. O/C OUT * * * LED BO 63 24 2 Yes
2665 67-1 TRIP (67-1 TRIP) 67 Direct. O/C OUT * on m LED BO 63 25 2 Yes
2668 67N-2 is BLOCKED (67N-2
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 94 1 Yes
2669 67-TOC is BLOCKED (67-TOC
BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 95 1 Yes
2670 67-TOC picked up (67-TOC
pickedup)
67 Direct. O/C OUT * On
Off
* LED BO 63 30 2 Yes
2674 67-TOC Time Out (67-TOC Time
Ou
t)
67 Direct. O/C OUT * * * LED BO 63 34 2 Yes
2675 67-TOC TRIP (67-TOC TRIP) 67 Direct. O/C OUT * on m LED BO 63 35 2 Yes
2676 67-TOC disk emulation is
ACTIVE (67-TOC DiskPU)
67 Direct. O/C OUT * * * LED BO
2677 67N-TOC is BLOCKED (67N-
TOC BLOCKED)
67 Direct. O/C OUT On
Off
On
Off
* LED BO 63 96 1 Yes
2679 67N-2 TRIP (67N-2 TRIP) 67 Direct. O/C OUT * on m LED BO 63 64 2 Yes
2681 67N-1 picked up (67N-1 picked
up)
67 Direct. O/C OUT * On
Off
* LED BO 63 41 2 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation