Appendix
A.9 Information List
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
672
2682 67N-1 Time Out (67N-1 Time
Out)
67 Direct. O/C OUT * * * LED BO 63 42 2 Yes
2683 67N-1 TRIP (67N-1 TRIP) 67 Direct. O/C OUT * on m LED BO 63 43 2 Yes
2684 67N-TOC picked up (67N-
TOCPickedup)
67 Direct. O/C OUT * On
Off
* LED BO 63 44 2 Yes
2685 67N-TOC Time Out (67N-TOC
TimeOut)
67 Direct. O/C OUT * * * LED BO 63 45 2 Yes
2686 67N-TOC TRIP (67N-TOC TRIP) 67 Direct. O/C OUT * on m LED BO 63 46 2 Yes
2687 67N-TOC disk emulation is
ACTIVE (67N-TOC Disk PU)
67 Direct. O/C OUT * * * LED BO
2691 67/67N picked up (67/67N
pickedup)
67 Direct. O/C OUT * On
Off
m LED BO 63 50 2 Yes
2692 67/67-TOC Phase A picked up
(67 A picked up)
67 Direct. O/C OUT * On
Off
* LED BO 63 51 2 Yes
2693 67/67-TOC Phase B picked up
(67 B picked up)
67 Direct. O/C OUT * On
Off
* LED BO 63 52 2 Yes
2694 67/67-TOC Phase C picked up
(67 C picked up)
67 Direct. O/C OUT * On
Off
* LED BO 63 53 2 Yes
2695 67N/67N-TOC picked up (67N
picked up)
67 Direct. O/C OUT * On
Off
* LED BO 63 54 2 Yes
2696 67/67N TRIP (67/67N TRIP) 67 Direct. O/C OUT * on m LED BO 63 55 2 Yes
2701 >79 ON (>79 ON) 79M Auto Recl. SP On
Off
**LEDBIBO4011Yes
2702 >79 OFF (>79 OFF) 79M Auto Recl. SP On
Off
**LEDBIBO4021Yes
2703 >BLOCK 79 (>BLOCK 79) 79M Auto Recl. SP On
Off
**LEDBIBO4031Yes
2711 >79 External start of internal A/R
(>79 Start)
79M Auto Recl. SP * On
Off
* LED BI BO
2715 >Start 79 Ground program
(>Start 79 Gnd)
79M Auto Recl. SP * on * LED BI BO 40 15 2 Yes
2716 >Start 79 Phase program (>Start
79 Ph)
79M Auto Recl. SP * on * LED BI BO 40 16 2 Yes
2720 >Enable 50/67-(N)-2 (override 79
blk) (>Enable ANSI#-2)
P.System Data 2 SP On
Off
**LEDBIBO40201Yes
2722 >Switch zone sequence coordi-
nation ON (>ZSC ON)
79M Auto Recl. SP On
Off
**LEDBIBO
2723 >Switch zone sequence coordi-
nation OFF (>ZSC OFF)
79M Auto Recl. SP On
Off
**LEDBIBO
2730 >Circuit breaker READY for re-
closing (>CB Ready)
79M Auto Recl. SP On
Off
**LEDBIBO40301Yes
2731 >79: Sync. release from ext.
sync.-check (>Sync.release)
79M Auto Recl. SP * on * LED BI BO
2753 79: Max. Dead Time Start Delay
expired (79 DT delay ex.)
79M Auto Recl. OUT on * * LED BO
2754 >79: Dead Time Start Delay (>79
DT St.Delay)
79M Auto Recl. SP On
Off
**LEDBIBO
2781 79 Auto recloser is switched OFF
(79 OFF)
79M Auto Recl. OUT on * * LED BO 40 81 1 Yes
2782 79 Auto recloser is switched ON
(79 ON)
79M Auto Recl. IntSP On
Off
* * LED BO 160 16 1 Yes
2784 79 Auto recloser is NOT ready
(
79 is NOT ready)
79M Auto Recl. OUT On
Off
* * LED BO 160 130 1 Yes
2785 79 - Auto-reclose is dynamically
BLOCKED (79 DynBlock)
79M Auto Recl. OUT On
Off
on * LED BO 40 85 1 Yes
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com